HT-Instruments COMBI 420

HT-Instruments Logo

HT-Instruments COMBI 420 Multifunction VDE 0100 Tester User Manual

Model: COMBI 420

1. Танилцуулга

This user manual provides comprehensive instructions for the safe and effective operation of the HT-Instruments COMBI 420 Multifunction VDE 0100 Tester. The COMBI 420 is an advanced and versatile instrument designed for quick and easy verification of electrical installations. It performs tests in accordance with VDE (EN61557) parts 2, 3, 4, 6, and 7, and includes single-phase network analysis capabilities. Please read this manual thoroughly before using the device to ensure proper functionality and user safety.

2. Аюулгүй байдлын мэдээлэл

Анхааруулга: Electrical testing can be hazardous. Always follow local safety regulations and procedures. Failure to do so may result in injury or damage to the equipment.

3. Бүтээгдэхүүн дууссанview

The HT-Instruments COMBI 420 is a robust and user-friendly multifunction tester. It features a large, clear LCD screen with backlight and a graphical help menu for intuitive operation.

HT-Instruments COMBI 420 Multifunction Tester

Figure 3.1: HT-Instruments COMBI 420 Multifunction Tester. The device features a large LCD display, navigation buttons, and input terminals for various measurements.

3.1 Гол онцлогууд

3.2 Багцын агуулга

The COMBI 420 package includes:

4. Тохиргоо

4.1 Батерей суурилуулах

The COMBI 420 requires 6 AA alkaline batteries. These are typically included with the device. To install or replace batteries:

  1. Төхөөрөмж унтарсан эсэхийг шалгана уу.
  2. Төхөөрөмжийн арын хэсэгт зайны тасалгааг ол.
  3. Тасалгааны тагийг нээ.
  4. Тасалгааны дотор заасан зөв туйлшралыг (+/-) ажиглаж 6 АА батерейг оруулна уу.
  5. Зайны тасалгааны тагийг сайтар хаа.

4.2 Connecting Test Leads and Accessories

Connect the appropriate test leads and accessories to the input terminals on the COMBI 420 based on the measurement you intend to perform. Always ensure connections are secure.

5. Ашиглалтын заавар

5.1 Асаах/унтраах

дээр дарна уу ХҮЧ button to turn the device on. The device will perform a self-test and display the main menu. To turn off, press and hold the ХҮЧ button, or allow the automatic shutdown feature to activate after a period of inactivity.

5.2 Navigation and Display

Use the directional buttons and the ENTER button to navigate through the menus and select functions. The large LCD screen displays measurement results, settings, and the graphical help menu. Press ESC/MENU to return to the previous menu or access the main menu. The ТУСЛАХ button provides on-screen assistance for current functions.

5.3 Хэмжилтийн функцууд

The COMBI 420 offers a wide range of measurement capabilities. Always refer to the on-screen help or specific sections of this manual for detailed connection diagrams and procedures for each test.

  1. Low-Ohm Measurement (Continuity):

    Measures resistance with a test current of >200 mA DC, compliant with VDE 0413 part 4 (EN 61557-4). Used to verify the continuity of protective conductors and equipotential bonding.

  2. Тусгаарлалтын туршилт:

    Performs insulation resistance measurements at 50, 100, 250, 500, or 1000 V DC, compliant with VDE 0413 part 2 (EN 61557-2). Essential for checking the integrity of insulation in electrical systems.

  3. FI (RCD) Test and Analysis:

    Comprehensive testing of Residual Current Devices (RCDs) according to VDE 0413 part 6 (EN 61557-6). Includes trip time, trip current, and contact voltage хэмжилт.

  4. Loop and Network Impedance Measurement:

    Measures loop impedance and network impedance, compliant with VDE 0413 part 3 (EN 61557-3). This is crucial for determining prospective fault current and ensuring proper circuit breaker operation.

  5. Short-Circuit Current Ik Display:

    Displays the calculated prospective short-circuit current (Ik) based on impedance measurements, as per VDE 0413 part 3 (EN 61557-3).

  6. Loop Resistance without RCD Tripping:

    Allows loop resistance measurement in circuits protected by RCDs without causing the RCD to trip, using a low test current.

  7. Rotating Field Direction Measurement:

    Determines the phase sequence (rotating field direction) in three-phase systems, compliant with VDE 0413 part 7 (EN 61557-7). This can be performed even with a single test probe.

  8. Power Measurement and Harmonic Analysis:

    Measures active, reactive, and apparent power, as well as power factor. Performs harmonic analysis of voltage and current up to the 49th harmonic and calculates Total Harmonic Distortion (THD) in percentage.

  9. External Probe Measurements:

    When connected, the device can display readings from external humidity, temperature, light (lux), and sound level probes.

5.4 Өгөгдөл хадгалах ба дамжуулах

The COMBI 420 has an internal memory capable of storing up to 600 measurement values. Use the ХАДГАЛАХ button to store current measurement results. Data can be transferred to a PC using the integrated optical USB interface and the provided Topview програм хангамж.

6. Засвар үйлчилгээ

6.1 Цэвэрлэгээ

Clean the device regularly with a soft, dry cloth. Do not use abrasive cleaners or solvents. Ensure no moisture enters the device.

6.2 Батерейг солих

Replace batteries when the low battery indicator appears on the display. Refer to Section 4.1 for battery installation instructions. Always use new, high-quality AA alkaline batteries.

6.3 Шалгалт тохируулга

For continued accuracy and compliance, periodic calibration by an authorized service center is recommended. The device is supplied with an ISO 9000 calibration protocol, indicating its initial calibration status.

7. Алдаа засах

If you encounter issues with your COMBI 420, try the following basic troubleshooting steps:

For more complex issues, utilize the device's built-in graphical help menu or contact HT-Instruments technical support.

8. Техникийн үзүүлэлтүүд

ОнцлогТодорхойлолт
Загварын дугаарКОМБИ 420
ҮйлдвэрлэгчHT-Instruments
Бүтээгдэхүүний хэмжээ (L x W x H)24 x 17 x 8 см (ойролцоогоор 9.45 x 6.69 x 3.15 инч)
Жин3 кг (ойролцоогоор 6.6 фунт)
Эрчим хүчний эх үүсвэрBattery-Powered (6 AA batteries required, included)
Аюулгүй байдлын дагаж мөрдөхIEC-1010-1, CAT III 415 V
Хэмжилтийн стандартуудVDE (EN61557) parts 2, 3, 4, 6, 7
Дотоод санах ой600 хэмжилтийн утга
ИнтерфэйсОптик USB
Оруулсан бүрэлдэхүүн хэсгүүдТопview software, USB cable, storage bag, measurement cable with earthed plug, 3 safety test leads, 2 test probes, 3 crocodile clips, batteries, user manual, ISO 9000 calibration protocol

9. Баталгаат хугацаа ба дэмжлэг

HT-Instruments products are manufactured to high quality standards. For specific warranty information, please refer to the documentation included with your purchase or visit the official HT-Instruments website. For technical support, service, or inquiries regarding calibration, please contact your local HT-Instruments distributor or customer service department.