1. Танилцуулга

The Fieldpiece DR58 Heated Diode Refrigerant Leak Detector is an ultra-sensitive tool designed for HVACR professionals to quickly and accurately locate refrigerant leaks. Utilizing a heated diode sensor, it detects a wide range of refrigerants with high precision. This manual provides essential information for the proper setup, operation, maintenance, and troubleshooting of your DR58 leak detector.

Fieldpiece DR58 халаалттай диодын хөргөлтийн алдагдлыг илрүүлэгч

Image 1.1: The Fieldpiece DR58 Heated Diode Refrigerant Leak Detector, showing its main body and flexible probe.

2. Үндсэн шинж чанарууд

The DR58 is equipped with several features to enhance leak detection efficiency:

  • Ultra-Sensitive Heated Diode Sensor: Detects micro leaks as small as <0.03 oz/yr, offering 20 times greater sensitivity than traditional bubble methods.
  • Universal Refrigerant Compatibility: Capable of detecting all HFC, CFC, HCFC, HFO, H2N2 (Tracer Gas), and blended refrigerants used in HVACR systems.
  • Бат бөх, удаан эдэлгээтэй: Features an IP54 rating for resistance against moisture and oil, ensuring reliability in various working conditions. The sensor has a typical life of 300 hours.
  • Clear Leak Indicators: A large, backlit LCD screen displays leak size and intensity using a bar graph and numeric readings. An LED tip and audible beep provide immediate feedback for precise leak pinpointing.
  • Flexible Probe and Extended Battery Life: A 17-inch flexible probe allows access to tight spaces. The rechargeable USB battery provides up to 18 hours of continuous operation. Replaceable filter tips are included.
Features and Benefits of Fieldpiece DR58

Image 2.1: Visual summary of the DR58's features, including its heated diode sensor, backlit LCD, refrigerant compatibility, and durable design.

3. Тохиргоо

Before initial use, ensure the DR58 is properly set up and charged.

3.1 Сав баглаа боодол ба эд ангиуд

Your Fieldpiece DR58 package should include:

  • 1 x Heated Diode Refrigerant Leak Detector (DR58)
  • 5 x Replacement Filtered Tips (RFT6)
  • 1 x Blow-Molded Case
  • 1 x Heated Diode Sensor (RHD1) (pre-installed or separate)
  • 1 x USB Charging Cable and Wall Adapter
What's Included with Fieldpiece DR58

Image 3.1: Contents of the DR58 package, showing the detector, charging cable, filter tips, and case.

3.2 Анхны цэнэглэлт

  1. Connect the USB charging cable to the DR58's charging port.
  2. Plug the other end of the cable into the wall adapter and then into a power outlet.
  3. Allow approximately 6 hours for a full charge. The battery indicator on the LCD will show charging status.

3.3 Sensor and Filter Tip Installation

  1. Төхөөрөмж унтарсан эсэхийг шалгана уу.
  2. If the heated diode sensor (RHD1) is not already installed, carefully insert it into the end of the flexible probe until it clicks into place.
  3. Screw a filtered tip onto the end of the sensor. Ensure it is finger-tight to prevent debris from entering the sensor.

4. Үйл ажиллагаа

Follow these steps for effective leak detection with your DR58.

4.1 Асаах болон халаах

  1. Press and hold the power button (blue button with sun icon) for approximately 1 second to turn on the device.
  2. The DR58 will display 'Warm' and then 'AZERO' as it warms up and performs an automatic zeroing. This process typically takes less than 10 seconds.

4.2 Төхөөрөмжийг тэг болгох

Zeroing establishes a baseline for the ambient air, allowing the detector to accurately identify refrigerant concentrations above this baseline.

  • Автомат тэглэх: The device automatically zeros upon power-on and continuously adjusts to background refrigerant levels during operation.
  • Гараар тэглэх: To manually zero the device, move the probe to an area known to be free of refrigerant. Press the 'ZERO MANUAL/AUTO' button. The display will show 'AZERO' to confirm.

4.3 Мэдрэмжийг тохируулах

The DR58 offers adjustable sensitivity levels to suit different leak detection scenarios.

  • Press the 'SENSITIVITY MAX ON/OFF' button to cycle through sensitivity levels (High, Medium, Low).
  • Use higher sensitivity for smaller leaks or when the leak source is difficult to pinpoint. Use lower sensitivity in areas with higher background refrigerant levels to avoid false positives.

4.4 Нэвчилт илрүүлэх журам

  1. Slowly move the flexible probe along the suspected leak area, such as refrigerant lines, coils, and connections. Maintain a consistent speed of approximately 1-2 inches per second.
  2. Observe the LCD display for increasing bar graph segments and numeric readings, indicating the presence of refrigerant.
  3. Listen for the audible beep, which will increase in frequency and pitch as the leak source is approached.
  4. The LED tip on the probe will also illuminate red, intensifying as the leak concentration increases.
  5. Once a leak is detected, move the probe away from the area and then slowly re-approach to confirm the exact location.
DR58 probe tip with illuminated LED

Image 4.1: Close-up of the DR58's flexible probe tip, showing the illuminated red LED indicator during leak detection.

Video 4.1: An official product video demonstrating the Fieldpiece DR58 leak detector in use, highlighting its features and effectiveness in finding refrigerant leaks.

5. Засвар үйлчилгээ

Regular maintenance ensures the longevity and accuracy of your DR58.

5.1 Replacing Filter Tips

The filter tips prevent debris from entering the sensor. Replace them regularly, especially in dirty environments, or if they appear clogged.

  1. Unscrew the old filter tip from the sensor.
  2. Screw on a new replacement filter tip (RFT6) until it is finger-tight.

5.2 Мэдрэгч солих

The heated diode sensor (RHD1) has a typical life of 300 hours. Replace the sensor when its performance degrades or if the device indicates a sensor error.

  1. Power off the DR58.
  2. Unscrew the filter tip.
  3. Gently pull the old sensor out of the probe.
  4. Insert the new RHD1 sensor into the probe until it clicks into place.
  5. Re-attach a clean filter tip.

5.3 Цэвэрлэгээ

  • Зар сурталчилгаагаар төхөөрөмжийн гадна талыг арчихamp даавуу. Зүлгүүрийн цэвэрлэгч, уусгагчийг бүү ашигла.
  • Ensure the sensor and filter tip are free from oil, moisture, and debris.

6. Алдаа засах

If you encounter issues with your DR58, refer to the following common problems and solutions.

АсуудалБоломжит шалтгаанШийдэл
Төхөөрөмж асахгүй байна.Батарей бага эсвэл цэнэггүй болсон.Charge the device using the provided USB cable and adapter.
Буруу эсвэл зөрүүтэй уншилтууд.Sensor contaminated or worn out; filter tip clogged; high background refrigerant.Replace filter tip. Replace sensor if necessary. Perform manual zeroing in a clean air environment.
No leak detected despite suspected leak.Low sensitivity setting; probe moved too quickly; sensor issue.Increase sensitivity. Move probe slower. Check and replace sensor if needed.
Constant alarm or high readings in clean air.Device not properly zeroed; sensor contaminated.Perform manual zeroing in a clean air environment. Clean or replace sensor.

7. Техникийн үзүүлэлтүүд

Technical specifications for the Fieldpiece DR58 Heated Diode Refrigerant Leak Detector.

Fieldpiece DR58 Specifications

Image 7.1: A detailed list of the DR58's technical specifications, including sensor type, sensitivity, and battery life.

ТодорхойлолтҮнэ цэнэ
Мэдрэгчийн төрөлХалаасан диод мэдрэгч
Мэдрэгчийн амьдралЕрдийн 300 цаг
Мэдрэмжийн түвшинӨндөр, дунд, бага (сонгож болно)
Мэдрэмжийн хамгийн дээд хэмжээ0.03 oz/yr (1g/a) stationary; 0.1 oz/yr (3g/a) in motion
Detection FeedbackУлаан үзүүртэй LED, LCD бар график, LCD цифрүүд, дохио
ХөргөгчHFC, HCFC, CFC, HFOs, холимог
Хариу өгөх хугацааЕрдийн <1 секунд
Сэргээх хугацааЕрдийн <10 секунд
Зайны төрөл3.7 VDC (нэрлэсэн) 2550mAh, орлуулах боломжгүй
Цэнэглэх хугацаа6 hours typical with included charger
Зайны ашиглалтЕрдийн 18 цаг, арын гэрэлтүүлэг унтарсан
Автомат унтраалтИлрүүлэх, товчлуур дарахгүйгээр 10 минут
Үйл ажиллагааны орчин32°F - 104°F (0°C - 40°C); < 75% RH (конденсацгүй)
Хадгалах температур-4°F - 140°F (-20°C - 60°C); <80% RH
Жин14 унци (400г)
Усны эсэргүүцэлIP54 стандартад зориулагдсан
Бүтээгдэхүүний хэмжээс10 x 8 x 10 инч

8. Баталгаат хугацаа ба дэмжлэг

Fieldpiece Instruments provides a warranty for its products against defects in material and workmanship. For specific warranty terms, registration, and technical support, please refer to the official Fieldpiece webсайт эсвэл харилцагчийн үйлчилгээтэй шууд холбогдоно уу. Худалдан авалтын баримтаа худалдан авалтын баталгаа болгон хадгалаарай.

Нэмэлт тусламж авахыг хүсвэл зочилно уу Fieldpiece Store on Amazon or the official Fieldpiece webсайт.

Холбогдох баримт бичиг - DR58

Урьдчилсанview Fieldpiece DR58 Халаалтын Диодтой Хөргөлтийн Алдагдал Илрүүлэгчийн Ашиглалтын Гарын Авлага
Fieldpiece DR58 халаалттай диодтой хөргөлтийн алдагдал илрүүлэгчийн операторын гарын авлага, түүний онцлог шинж чанар, техникийн үзүүлэлт, ажиллагаа, суурилуулалт, засвар үйлчилгээ, янз бүрийн хөргөлтийн бодисыг илрүүлэх ажиллагааны туршилтыг дэлгэрэнгүй харуулсан.
Урьдчилсанview Fieldpiece DRX3 хөргөлтийн шингэний алдагдал илрүүлэгчийн ашиглалтын гарын авлага
Comprehensive operator's manual for the Fieldpiece DRX3 Refrigerant Leak Detector, detailing its features, operation, safety precautions, maintenance, and specifications for HVAC professionals.
Урьдчилсанview Fieldpiece DR82 Infrared Refrigerant Leak Detector Operator's Manual
Comprehensive guide to the Fieldpiece DR82 Infrared Refrigerant Leak Detector, covering its features, specifications, operation, maintenance, and warranty. Learn how to detect HFC, HCFC, CFC, HFO, and blend refrigerants with high sensitivity and multiple indicators.
Урьдчилсанview Fieldpiece DR82 Infrared Refrigerant Leak Detector Operator's Manual
Operator's manual for the Fieldpiece DR82 Infrared (IR) Refrigerant Leak Detector. Details features, specifications, operation, maintenance, safety guidelines, and warranty information for HVACR professionals.
Урьдчилсанview Fieldpiece DR82 Infrared Refrigerant Leak Detector Operator's Manual
Comprehensive operator's manual for the Fieldpiece DR82 Infrared (IR) Refrigerant Leak Detector, detailing its features, operation, maintenance, and specifications for HVACR professionals.
Урьдчилсанview Fieldpiece DRX3 Refrigerant Leak Detector Operator Manual
Comprehensive operator manual for the Fieldpiece DRX3 Refrigerant Leak Detector, detailing its features, operation, maintenance, and safety guidelines for detecting refrigerant and combustible gas leaks.